More transparency – with KSB Guard
Even high-quality pumps can sometimes experience malfunctions whose exact cause can only be determined by a long-term diagnosis. External factors are often to blame, and these can only be identified if the affected pump is monitored over a longer period of time using suitable sensor technology.
The project: Establishing the cause of pump failure
The customer: Abwasserverband Altenstadt
Pump-mounted sensor units in operation
The challenge: Determining external factors
The gateway for mobile reception in operation
The solution: Failure diagnosis via long-term measurement
Simply make a few basic data entries for each pump using your smartphone – done.
Figures I Data I Facts
End user: Abwasserverband Altenstadt
Starting point: Regular failures of 4 Sewatec D pumps
Vibration values measured prior to remedial measures: above 18 mm/s
Vibration values measured after remedial measures: below 1 mm/s
Cause: Incorrectly supported piping above the pumps
Tool used for pump monitoring: KSB Guard